# Condensate Lines Need to Be Accessible
### Issue Image:
![[Pasted image 20250207144045.png]]
## Issue Description:
- Condensate lines shall discharge to a tundish and be separated by an Air Gap.
- the tundish shall be accessible to allow regular inspection during operation.
- Note, [Allproof](https://allproof.com.au/product/gpo-tundish/) makes a handy option which can be installed inside of a wall.
## Actions to Prevent this Issue:
- [ ] Mechanical Engineer shall check that there are adequate tundishes to drain each air-conditioning unit.
- [ ] Architect shall coordinate with the Mechanical Engineer to ensure all AC units are drained.
## Source
AS3666.1 Air Handling and water systems of buildings - Microbial Control.