# Waterproofing Penetration Setout
### Issue Image:
![[Pasted image 20241112164849.png | Floor Waste and Pipes]]
![[Pasted image 20241112164546.png|Pipes Too Close]]
## Issue Description:
- Services shall offset minimum 100mm other vertical services either walls or other service penetrations.
- This gap is required to ensure there is space for wateproofing membranes can applied properly. There should be enough room for the largest of either the tool required to apply it or the puddle flange/service itself.
## Actions to Prevent this Issue:
- [ ] Architect to check that all service penetrations have minimum 100mm clearance from other vertical faces.
- [ ] Service Engineers to detail at 1:20 areas that are clustered with multiple penetrations like service cupboard risers.